Electrical Specifications & Physical Specifications
|
| Operating Temperature Range: 2W-B and 4W-B: 32°F–120°F (0°C–49°C) |
-- 2WT-B and 4WT-B: 32°F–100°F (0°C–37.8°C)
|
Operating Humidity Range: 0 to 95% RH non-condensing
|
Thermal Sensor: 135°F (57.2°C) fixed
|
Freeze Trouble: 2WT-B and 4WT-B only: 41°F (5°C)
|
Sensitivity: 2.5%/ft. nominal
|
Input Terminals: 14–22 AWG
|
| Dimensions (including base): 5.3 inches (127 mm) diameter |
-- 2.0 inches (51 mm) height
|
Weight: 6.3 oz. (178 grams)
|
| Mounting: 31⁄2-inch octagonal back box |
| 4-inch octagonal back box |
| Single gang back box |
4-inch square back box with a plaster ring
|
Direct mount to ceiling
|
| Operating Voltage: Nominal: 12/24 V non-polarized |
| Min.: 8.5 V |
| Max.: 35 V |
| Maximum Ripple Voltage: 30% peak to peak of applied voltage |
| Standby Current: 2-wire: 50 ìA maximum average |
4-wire: 50 ìA maximum average
|
| Maximum Alarm Current: 2-wire: 130 mA limited by control panel |
4-wire: 20 mA @12V, 23mA @ 24V
|
| Peak Standby Current: 2-wire: 100 ìA |
4-wire: n/a
|
| Alarm Contact Ratings: 2-wire: n/a |
4-wire: 0.5 A @ 30V AC/DC
|
LED Modes Power Up Sequence for LED Indication
|
| LED Mode Green LED Red LED Condition Duration |
| Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds |
| Normal (standby) Blink every 5 seconds off |
| Out of sensitivity off Blink every 5 seconds |
| Freeze trouble off Blink every 10 seconds |
| Alarm of f Solid |