The SpectrAlert Advance series of notification appliances is designed to simplify installations, with features such as plug in designs, instant feedback messages to ensure correct installation of individual devices, and 11 field-selectable candela settings for wall and ceiling strobes and horn/strobes.

When installing Advance products, first attach a universal mounting plate to a four-inch square, four-inch octagon or double-gang junction box. The two-wire mounting plate attaches to a single-gang junction box. Next, connect the notification appliance circuit wiring to the SEMS terminals on the mounting plate.

Finally, attach the horn, strobe or horn/strobe to the mounting plate by inserting the product's tabs in the mounting plate's grooves. The device will rotate into position, locking the product's pins into the mounting plate's terminals. The device will temporarily hold in place with a catch until it is secured with a captured mounting screw. The SpectrAlert Advance series includes outdoor notification appliances. Outdoor strobes and horn/strobes (two wire and four wire) are available for wall or ceiling. Outdoor horns are available for wall only. All System Sensor outdoor products are rated between minus 40 degrees Fahrenheit and 151 degrees Fahrenheit in wet or dry applications.

Features

  • Electrically compatible with existing SpectrAlert products
  • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela
  • Plug-in design
  • Field selectable candela settings on wall and ceiling units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185
  • Same mounting plate for wall- and ceiling-mount units
  • Shorting spring on mounting plate for continuity check before installation
  • Tamper resistant construction
  • Outdoor wall and ceiling products rated from 40F to 151F
  • Design allows minimal intrusion into the back box
  • Horn rated at 88+ dbA at 16 volts
  • Rotary switch for horn tone and three volume selections
  • Outdoor products UL listed to UL 1638 (strobe) and UL 464 (horn) outdoor requirements
  • Outdoor products rainproof per UL 50 (NEMA 3R)
  • Compatible with MDL sync module
  • Specifications
  • Standard Operating Temperature 32F to 120F (0C to 49C)
  • K Series Operating Temperature 40F to 151F (40C to 66C)
  • Humidity Range 10 to 93% non-condensing (indoor products)
  • Strobe Flash Rate 1 flash per second
  • Nominal Voltage Regulated 12DC/FWR or regulated 24DC/FWR1
  • Operating Voltage Range2 8 to 17.5 V (12V nominal) or 16 to 33 V (24 nominal)
  • Input terminal wire gauge 12 to 18 AWG
  • Ceiling mount dimensions (including lens) 6.8 diameter x 2.5 high (173 mm diameter x 64 mm high)
  • Wall mount dimensions (including lens) 5.6L x 4.7W x 2.5D (142 mm L x 119 mm W x 64 mm D)
  • Horn dimensions 5.6L x 4.7W x 1.3D (142 mm L x 119 mm W x 33 mm D)
  • Wall-mount back box skirt dimensions (BBS-2, BBSW-2) 5.9L x 5.0W x 2.2D (151 mm L x 128 mm W x 56 mm D)
  • Ceiling-mount back box skirt dimensions (BBSC-2, BBSCW-2) 7.1 diameter x 2.25 high (180 mm diameter x 57 mm high)
  • Wall-mount weatherproof back box dimensions (SA-WBB) 5.7L x 5.1W x 2.0D (145 mm L x 130 mm W x 51 mm D)
  • Ceiling-mount weatherproof back box dimensions (SA-WBBC) 7.1 diameter x 2.0 high (180 mm diameter x 51 mm high)
    Engineering Specification General SpectrAlert Advance horns, strobes and horn/strobes shall mount to a standard 4 x 4 x 1-inch back box, 4-inch octagon back box or double-gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 1-7/8 inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync.Circuit. Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between nine and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 17 and 33 volts. Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC, or full-wave rectified, unfiltered power supply. Strobes and horn/strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, 185.

    Strobe The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.

    Horn/Strobe Combination The horn/strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn/strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three-pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn on horn/strobe models shall operate on a coded or non-coded power supply.

    Outdoor Products SpectrAlert Advance outdoor horns, strobes and horn/strobes shall be listed for outdoor use by UL and shall operate between minus 40 degrees and 151 degrees Fahrenheit. The products shall be listed for use with a System Sensor outdoor/weatherproof back box with half inch and three-fourths inch conduit entries.

    Synchronization Module The module shall be a System Sensor Sync.Circuit model MDL listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn/strobe models over a single pair of wires. The module shall mount to a 4-11/16 x 4-11/16 x 2-1/8 inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.